Control unit Micro-ETB/H AF-X – activates 1 afx generator
PRODUCT CODE: MBK25-CONTROL-ETB/H
ERP: 0135950
Please login first to see this content
Product information
- easy connection through push connection
a bridging protection ensures that the ignition current flows through ALL electrical activators for at least 50 ms, also when one of the igniters is malfunctioning or behaving differently than others (eg. igniting sooner) and going in high impedance before other igniters are ignited) - the μ-ETB is equipped with a switch that activates the end-line monitoring diode at the last extinguishing generator
- a second switch is intended to disconnect the electrical activator from the extinguishing line for the purpose of testing the extinguishing line without activating the extinguishing generators
- there is a red test LED that shows that an activation current is actually being initiated during the installation test
- the μ-ETB is equipped with reverse polarity protection, thereby avoiding connection errors
- the μ-ETB is equipped with surge protection, which reduces the risk of activation of a fire generator near a lightning strike
Characteristics